6. PHOTOELECTRIC CONTROL UNIT (PECU)
|
|
The PECU is classified as a Class II PECU. It is manufactured to IP65 classified in accordance to degree of protection against ingress of dust and moisture and tested to IEC 529:1989-11.
There are 2 version (Electronically Relay Control Version or Electronically Solid Control Version)
|
| |
|
| |
| Version |
1. Electronically Relay Control |
2. Electronically Solid Control |
| Type |
Normally Close Circuit |
Normally Open Circuit |
| Maximum rating |
10Amp, 240V, 50Hz |
2Amp (RES) 240V, 50Hz. 10Amp (IND) |
| Classification |
Class II PECU or Socket |
| Model |
AR 10PCU-E-NC (Nema Type) |
| Packing Details |
Quantity: 100 pcs/ctn
Dimension: 725mm x 725mm x 600mm
Net Weight: 25kg
Gross Weight:
26.75kg |
|
| |

|
| Version |
1. Electronically Relay Control |
| Type |
Normally Close Circuit |
| Maximum rating |
10Amp, 240V, 50Hz |
| Classification |
Class II PECU |
| Model |
AR 10PCU-E-NC (Round Type) |
| Packing Details |
Quantity:100 pcs/ctn
Dimension: 340mm x 340mm x 300mm
Net Weight: 12kg
Gross Weight: 13.50kg
|
|
|
| |
Technical Performances
 |
Rated Supply Voltage |
: 240 VAC |
 |
Perm Voltage Fluctuations |
: 170-265 VAC |
 |
Protection |
: IP 65 |
 |
Dust & Moisture |
: IEC 529:1989-11 |
 |
Standards |
: BS 5972:1980 + Amd.1:1982 and Amd2:1984 BS 4533 |
 |
Photometric Performance |
: Declared Switch-ON Level: 50 LUX ± 20%
Declared Switch-OFF Level: 100 LUX ± 20% |
|